Double Flange Expansion Joint Dimensions

PN16 flanges (EN 1092-1, same drilling as GB/T 9124.1 and DIN). All dimensions in mm. L is the installation length at half stroke; ΔL is the total axial stroke.

Swipe the table →

DNInchLength and strokeFlange PN16 (EN 1092-1 = GB = DIN)Bolts
LStroke ΔLL min – maxODBolt circleHoles
652½"34050315 – 3651851458 × Ø18M16
803"34050315 – 3652001608 × Ø18M16
1004"34050315 – 3652201808 × Ø18M16
1255"34050315 – 3652502108 × Ø18M16
1506"34050315 – 3652852408 × Ø22M20
2008"34050315 – 36534029512 × Ø22M20
25010"34050315 – 36540535512 × Ø26M24
30012"35065317.5 – 382.546041012 × Ø26M24
35014"35065317.5 – 382.552047016 × Ø26M24
40016"35065317.5 – 382.558052516 × Ø30M27
45018"35065317.5 – 382.564058520 × Ø30M27
50020"35065317.5 – 382.571565020 × Ø33M30
60024"35065317.5 – 382.584077020 × Ø36M33
70028"35065317.5 – 382.591084024 × Ø36M33
80032"590130525 – 655102595024 × Ø39M36
90036"590130525 – 6551125105028 × Ø39M36
100040"590130525 – 6551255117028 × Ø42M39
120048"590130525 – 6551485139032 × Ø48M45
140056"590130525 – 6551685159036 × Ø48M45
160064"590130525 – 6551930182040 × Ø56M52
180072"590130525 – 6552130202044 × Ø56M52
200080"590130525 – 6552345223048 × Ø62M56
DN2200 – DN3600 (PN10 / PN6) and the full PN6 / PN10 / PN25 tables are in the datasheet below.

DN2200 – DN3600 (PN10 / PN6) and the full PN6 / PN10 / PN25 tables are in the datasheet below.

Longer stroke and other lengths on request.

How It’s Built

Six parts. The gasket seals while the spigot slides; the limit studs set how far it can open.

Expansion Joint or Dismantling Joint?

Built like our dismantling joint, but longer and with limit studs instead of tie studs. It moves — so the pipe needs anchors.

Swipe the table →

Double flange expansion jointDouble flanged dismantling joint
RodsLimit studs; the outside nuts are set at the end of the strokeLong tie studs through both end flanges and the gland, nuts locked at every flange
Pressure thrustMust be held by pipe anchorsCarried by the tie studs
Movement in serviceAxial stroke ΔL, 50–140 mm by sizeNone once locked — works as a rigid spool
At installationPulled to half stroke, then limit nuts setAdjusted within ΔL (40–80 mm), then locked
Installation length L340–600 mm200–450 mm
Anchors at the jointNeeded on both sidesNot needed for the thrust
Main jobTaking expansion and contraction of straight runsFitting and removing valves, pumps and meters

Choose a dismantling joint when

Choose an expansion joint when

Materials, Gasket and Coating

Standard materials are below. Tell us the medium and where the pipe runs, and we match the gasket and finish.

PartStandardOptions
Body and glandQ235 carbon steelDuctile iron QT400-15; cast steel ZG230-450; 20# steel; SS304 / SS316L
Flanged spigotQ235 steel pipe + flange20# or Q355 (16Mn) steel; SS304 / SS316L
GasketNBREPDM (drinking water); other rubbers on request
Studs and nutsQ235 / 35# carbon steel, zinc platedStainless steel 304 / 321 (1Cr18Ni9Ti)
CoatingEpoxy, blueRed epoxy; hot-dip galvanising; no coating on stainless joints

NBR gasket (standard)

For: water, sewage, oil, fuel, low-pressure gas.
Temperature: −10 to +80 °C
Not for: lines that need a drinking-water rubber.

EPDM gasket

For: drinking water, hot water, sea water.
Temperature: −20 to +90 °C
Not for: oil and fuel.

Finish

Blue or red epoxy: buried lines, valve chambers, pump houses.
Stainless steel: sea water and chemical plants.
Galvanised: outdoor pipework.

The gasket is the only rubber part. Choose it by the medium; choose the finish by where the joint is installed.

Pressure and Temperature

Choose the class by working pressure. Every joint is hydrostatically tested before coating.

Pressure classes

ClassWorking pressureShell test (1.5×)Seal test (1.1×)
PN60.6 MPa0.9 MPa0.66 MPa
PN101.0 MPa1.5 MPa1.1 MPa
PN161.6 MPa2.4 MPa1.76 MPa
PN25*2.5 MPa3.75 MPa2.75 MPa

* PN25 on request.

Temperature

−10 to +80 °C with the standard NBR gasket; EPDM up to +90 °C on water.

Media

Water, drinking water, sea water, sewage, oil; gas at low pressure.

Pressure class by size

SizeStandard class
DN65 – DN1000PN16 (PN25 on request)
DN1200 – DN2000PN16
DN2200 – DN3000PN10
DN3200 – DN3600PN6

The pressure class sets the body and flange thickness. The thrust on the anchors grows with pressure — see the anchor load table below.

How Much Stroke, How Strong the Anchors

Two numbers to check before you order: the movement of your pipe, and the force your anchors must hold.

Movement calculator

Total movement
Stroke of this size
At installation, leave room to close (expansion)
…and room to open (contraction)

Anchor load from pressure thrust (kN)

SizePN10PN16PN25
DN100101626
DN150223656
DN200386094
DN30083133207
DN400143228356
DN500221353552
DN600312499779
DN8005288451,320
DN10008171,3072,043
DN12001,1691,8702,922

F = P × π/4 × D², with D = spigot outside diameter. This is at working pressure — multiply by 1.5 for the test, and add guide friction. The anchors, not the limit studs, must hold it.

Flange Standards and Materials

Pick your pipe’s flange standard, class and size. If the numbers match your flange, our joint bolts straight on — no adapter, no re-drilling.

Check your flange

Flange OD — D
Bolt circle — K
Bolt holes — n × d
Bolt size
Flange thickness — t*

Standards we drill to

  • EN 1092-1 / DIN
    PN6 · PN10 · PN16 · PN25 · PN40 — DIN was replaced by EN 1092-1 with the same drilling; BS 4504 too
  • GB/T 9124.1 (PN)
    PN6 · PN10 · PN16 · PN25 · PN40 (GB/T 9119 plate flanges) — same drilling as EN 1092-1; Class flanges to GB/T 9124.2 = ASME B16.5
  • ASME B16.5 / B16.47
    Class 150 · Class 300 · Series A 26"–60"; AWWA C207 Class D
  • JIS B2220
    5K · 10K · 16K · 20K
  • AS 2129 / AS 4087
    Table D · Table E · PN16
  • Your drawing
    GOST, BS 10 or any special drilling; tapped holes on request

Flange drilling chart

EN · ASME · JIS · AS — OD, bolt circle, holes, thickness

Flange material and finish

Installing a Double Flange Expansion Joint

Four steps. The order matters: flanges first, then seal, then lock.

Anchor both sides

Under pressure the joint pushes the pipes apart. Anchors take that force; above ground, fix supports at both ends.

Install at half stroke

Loosen the gland, pull the joint to half its stroke, tighten the gland diagonally, then set the limit nuts.

Keep the pipe on one axis

Put guides close to the joint. It takes axial movement only — never load it off-centre.

Leave the limit nut gap

The gap is the extension still available. Never tighten limit nuts against the flange.

Options

Add these when the job needs them — each one is priced separately.

Stainless steel

Body, spigot, gland and studs in stainless steel, for sea water and chemical plants.

Blue or red epoxy

Epoxy coated inside and out, in blue or red; hot-dip galvanising on request.

Long stroke / custom length

Longer stroke for long pipe runs, or a length made to your gap.

Two drilling standards

One end EN, the other ASME, JIS or AS — for joining old and new equipment.

Why Buy From Our Factory

This is simple steelwork. What decides whether it works on site is the right length, the right drilling and rods sized for the pressure — then the price.

Length and drilling confirmed first

Face-to-face length, setting range and the drilling of both flanges are checked against your drawing and sent back for approval before we cut steel.

Thrust checked, not guessed

Tie studs on our dismantling joints are checked against the pressure thrust at test pressure; for expansion joints we give you the anchor load. Both are in the datasheet.

Pressure tested before coating

Every joint is hydrostatically tested at 1.5 × PN, then blasted and coated

Factory price, quoted the same day

You buy from the production line, not through a trader. Send size, pressure and gap, and get a price the same working day.

Where It’s Installed

Long pipe runs

Between two anchors on water, heating and process lines, it takes the length change from temperature.

Valve lines

Beside valves and pumps that sit on their own supports; makes fitting and removal easier.

Pipe bridges

Where a pipe crosses a river or road between two piers, anchored at each pier.

In Service

Dismantling and expansion joints from our factory, photographed by customers on site.

Double Flange Expansion Joint Price

What you pay depends on a few choices. Send them and we quote the same day.

What changes the price

Reference price

PN16, Q235 steel, NBR gasket, blue epoxy, EXW Gongyi. Prices change with steel costs — send your size and pressure and we quote the same day.

Downloads

Datasheets, drawings and references for submittals.

Control rods

Expansion joint datasheet

Dimensions PN6 / PN10 / PN16 / PN25, materials, tie stud check

2D drawing

Half-section with dimension table, opens in AutoCAD

For all our dismantling and expansion joints

Flange drilling chart

EN, ASME, JIS, AS — holes, bolt circle, thickness

Installation guide

Setting length, gland nuts, tie studs, anchors and guides

Frequently Asked Questions

What is the difference between an expansion joint and a dismantling joint?

The rods. A dismantling joint has long tie studs locked at every flange, so it is rigid and carries the pressure thrust. This expansion joint has limit studs whose outside nuts sit at the end of the stroke, so it moves — and needs anchors.

Total axial stroke 50 mm (DN65–DN250), 65 mm (DN300–DN700), 130 mm (DN800–DN2400) and 140 mm (DN2600–DN3600). Steel pipe grows about 0.012 mm per metre for every °C — use the calculator above.

Yes, on both sides. Each anchor must hold the pressure thrust shown in the anchor load table, plus guide friction. Above ground, fix supports at both ends.

They stop the joint pulling apart if an anchor moves or during filling. They are not designed to carry the full pressure thrust.

No — axial movement only, and it must not be loaded off-centre. Keep the pipe straight with guides. For lateral or angular movement use a rubber expansion joint.

EPDM, up to +90 °C. The standard NBR gasket covers −10 to +80 °C. Tell us the highest temperature in the line.

MOQ 1 pcs. Common sizes ship in 5-7  days; large diameters and special drilling take 15-30 days.

Related Products

Double Flange Expansion Joint

Single Flange Expansion Joint

Detachable Dismantling Joint

Single Sphere Rubber Expansion Joint

Metal Expansion Joint

Flexible Metal Hose

Send Your Size, Pressure and Medium

We reply with a drawing and a price within 24 hours on working days.

Contact Us

Send your size, pressure, medium, flange standard and quantity. This block follows the clean contact layout of your reference page.

Free to Contact Us

Once we receive the detailed information regarding your request, your assigned customer representative will contact you shortly.

If you need help, please email us at sales1@lsrubberjoint.com

Download Now

Enter your name and email and the download starts right away.

If you need help, please email us at sales1@lsrubberjoint.com